R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
10
Fig. 6. Timer sequence for R4140G1106 Programmer.
Step-By-Step Operation (R4140G1106)
Start and Prepurge
0 secondsOn a call for heat, the burner controller
contacts close. If the limits and preignition interlocks
are closed and flame relay 2K is not holding in, relay 1K
pulls in through M7B, LS2, 2K2, and the LS HTR
(lockout switch heaterthus proving its continuity).
1K1 closes and 1K2 opens; timer motor starts
(through 1K1, M3A, and M5B); power is applied to
terminal 8, starting the burner motor (blower); 1K3
closes.
Prepurge begins.
4 secondsM10A closes, M10B opens; firing rate motor
drives toward high fire position (open).
M1B closes, bypassing 1K1; the timer can
complete its revolution if shutdown occurs.
9.5 secondsM7B opens; running interlocks must be
closed (airflow must be proven) or 1K drops out, 1K3
opens, and ignition trials cannot be started. Running
interlocks must remain closed through the Run period
or the system shuts down; the timer completes its
revolution and recycles the programmer.
15 secondsM11B closes; flame relay 2K can pull in if a
flame (or a condition simulating a flame) is detected. If
detected during prepurge (until 57.5 seconds), 2K pulls
in, 2K2 opens, 1K drops out, and the system shuts
down; the timer completes its revolution and recycles
the programmer (if 2K dropped out).
45 secondsM10B closes; firing rate motor drives toward
low fire position (closed).
52 secondsM3A opens; timer stops until the low fire
proving switch closes; timer can be stopped by opening
the timer switch (until 66 seconds when M3A closes
again).
57.5 secondsM9A closes; the LS HTR (lockout switch
heater) begins heating in preparation for ignition trials.
M7A closes, bypassing the preignition interlocks.
M10052
TIMER
SECONDS
TIMER DIAL
TIMER
MOTOR
BURNER
MOTOR
(BLOWER)
INTERRUPTED
PILOT/IGNITION
MAIN FUEL
VALVE(S)
(GAS OR OIL)
FIRING RATE
MOTOR
SWITCHING
ACTUAL
DAMPER
OPERATION
0 10 20 30 40 50 60 70 80 90 100 110 120
START
STOP
START
STOP
START
STOP
IGN
PILOT
MAIN
PURGE
PREPURGE
6
PREIGNITION INTERLOCKS
RUNNING INTERLOCKS (PROVEN AIRFLOW)
MOTOR
DRIVES
DAMPER
OPEN
MOTOR
DRIVES
DAMPER
CLOSED
MOTOR DRIVES
DAMPER CLOSED
RUN
PERIOD
3
1
2
1
2
3
4
5
6
1
2
2
2
4
3
5
LOWLOW
15 SECONDS
10 SECONDS
7
8
5
12 TO 11
6
TERMINAL NUMBERS (CIRCLED).
SLOPE DEPENDS ON MOTOR TIMING.
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
PERIOD WHILE BURNER IS FIRING).
TIMER STOPS AT 164 SECONDS FOR THE RUN PERIOD WITH
THE BURNER FIRING.
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
HIGH FIRE POSITION
LOW FIRE POSITION
MODULATE
14 TO 11
10 TO 11