Chapter 4 Parameters|
Revision May 2008, ME14, SW V3.04 4-83
When Line Start Lockout is disabled (also known as Auto-Start), the drive will start when
powered-up with run commands applied. To start in Line Start Lockout mode, the AC drive
must see the run command go from stop to run after power up. When enabled, the AC drive
will not start when powered up if run commands were applied.
Pr. 147
Decimal Number of Accel / Decel Time
Factory Setting: 00
Settings 00 One Decimal
01 Two Decimals
It sets the number of decimals in the accel/decel time. It can be used for Acceleration /
Deceleration Time 1, Acceleration / Deceleration Time 2 and JOG Acceleration / Deceleration
Time.
Pr. 148
Number of Motor Poles
Settings 02 to 20 Factory Setting: 04
Pr. 149
Gear Ratio for Simple Index Function
Settings 4 to 1000 Factory Setting: 200
Pr. 150
Index Angle for Simple Index Function
Settings 00.0 to 360.0 Factory Setting: 180.0
Pr. 151
Deceleration Time for Simple Index Function
Factory Setting: 0.00
Settings 0.00 to 100.00 sec
0.00 Disable
This parameter should be used with Pr. 39-Pr.42 (setting 31).
Example: