30
Net Weight kg (lb)
W/O ISOTR
50 (110) 86.0 (189.2) 80(176)
Shipping Weight kg
(lb) W/O ISOTR
53 (116.7) 106.0 (233.2) 101.5(223.3)
Dimensions W x D
x H mm (inch) W/
ISOTR
257 x 590 x 700
(10.1"x23.2"x27.6")
342 x 690 x 715
(13.4" x 27.2" x
28.1")
Net Weight kg (lb)
W/ ISOTR
123.0 (270.6) 130 (286.0)
Shipping Weight kg
(lb) W/ ISOTR
145.0 (319.0) 151.5 (333.3)
Operating
Temperature
0~40°C / 32~104°F
Storage
Temperature
-20~50°C / -4~122°F
Altitude 3,500 meters max
Audible Noise (1
meter from surface)
50 dBA < 55 dBA
Environment
Relative Humidity 0 ~ 95% humidity, non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Conformance
Equipment
Protection Policy
Warranty policy may vary depends on region
Tower model (with LCD display) VGD-10000 VGD-12000 VGD-15000 VGD-20000
Capacity (VA) 10000VA 12000VA 15000VA 20000VA
Capacit
Capacity (W) 7000W 8400W 10500W 14000W
Voltage (on battery) 100V, 110V, 115V, 120V / 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)
Frequency (on
battery)
50 / 60 Hz +/-0.5%
Transfer Time 0 ms
Overload Recovery Auto transfer to UPS
High Efficiency
mode (AC to AC)
> 97 %
UPS Design
Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form Sine wave
Harmonic distortion < 3% of T.H.D. at linear load
Output
Crest Factor 3 : 1
Surge Protection IEC61000-4-5 level 3
Overload Protection
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150%
for 1.5 seconds (On-battery)
Protection and
Filtering
Short Circuit
Protection
UPS output cut off immediately or input fuse / circuit breaker protection
Visual Display (LED
model)
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency, on-line mode, back up mode, battery
capacity, load level
Audible Alarm
(Battery back-up)
Beep every 5 sec
UPS Fault Continuous beeping sound and LCD display
System/Displa
Warning
Communication RS-232 Serial Port and USB
Type Sealed, maintenance-free lead acid batteries
DC Voltage (V)
Battery (Tower )
240V / 12V9AH
x 20
240V / 12V7.2AH
x 20 x 2SET
240V / 12V7.2AH
x 20 x 2SET
240V / 12V9AH
x 20 x 2SET
Typical Recharge
Time to 90% Full
4 hours
Management Self-test, adjustable battery transfer points and alarm settings
Batter
Battery Protection Cut off without draining any current when battery is low
31
Cold Start (DC
start)
YES
Back Up Time
(Tower model)
About 4~6 min Full load / 10~15min Half load
Input Inlet Hardwire
Receptacles Hardwire
Dimensions W x D
x H mm (inch) W/O
ISOTR
257 x 690 x 715
(10.1" x 27.2" x
28.1")
342 x 690 x 905
(13.5"x27.2"x35.6")
342 x 760 x 905 (13.5" x 29.9" x 35.6")
Net Weight kg (lb)
W/O ISOTR
80 (176) 130 (286) 207 (455.4)
Shipping Weight kg
(lb) W/O ISOTR
101.5 (223.3) 151.5 (333.3) 225 (495.0)
Dimensions W x D
x H mm (inch) W/
ISOTR
342 x 690 x 715
(13.4" x 27.2" x
28.1")
342 x 690 x 905
(13.5"x27.2"x35.6")
342 x 760 x 905 (13.5" x 29.9" x 35.6")
Net Weight kg (lb)
W/ ISOTR
130 (286) 180 (396) 274 (602.8)
Physical
Shipping Weight kg
(lb) W/ ISOTR
151.5 (333.3) 201.5 (443.3) 292 (642.4)
Operating
Temperature
0~40°C / 32~104°F
Storage
Temperature
-20~50°C / -4~122°F
Altitude 3,500 meters max
Audible Noise (1
meter from surface)
< 55 dB
Environment
Relative Humidity 0 ~ 95% humidity, non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Conformance
Equipment
Protection Policy
Warranty policy may vary depends on region
For Rack mount model
RM model (with LCD display) VGD-4000 VGD5000 VGD-6000 VGD-10000
Capacity (VA) 4000VA 5000VA 6000VA 10000VA
Capacit
Capacity (W) 2800W 3500W 4200W 7000W
Voltage (on battery) 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)
Frequency (on
battery)
50 / 60 Hz +/-0.5%
Transfer Time 0 ms
Overload Recovery Auto transfer to UPS
High Efficiency
mode (AC to AC)
> 95 % > 97 %
UPS Design
Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form Sine wave
Harmonic distortion < 3% of T.H.D. at linear load
Output
Crest Factor 3 : 1
Surge Protection IEC61000-4-5 level 3
Overload
Protection
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150%
for 1.5 seconds (On-battery)
Protection and
Filtering
Short Circuit
Protection
UPS output cut off immediately or input fuse / circuit breaker protection
Visual Display
(LED model)
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency, on-line mode, back up mode, battery
capacity, load level
Audible Alarm
(Battery back-up)
Beep every 5 sec
System/Displa
Warning
UPS Fault Continuous beeping sound and LCD display