NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
26
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
Figure 14 AC Input Power Connection Routing Options
Figure 15 Installing Conduit Fittings when AC is Fed from the Top
Figure 16 AC Input Power Connections
Battery Compartment
Battery Compartment
AC enters at top.
AC enters at bottom.
AC enters at bottom.
AC enters at top.
65kAic
Circuit
Breaker
65kAic
Circuit
Breaker
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
Run AC Cables
from Top OR Bottom
Run AC Cables
from Top OR Bottom
1) Remove cover plate.
Note: Cut cover plate in half if
only one conduit being installed.
3) Secure conduit plate with conduit
fittings installed to top of cabinet.
Note: If only one conduit being installed,
re-install plate that was cut in half.
2) Install one or two customer provided
conduit fittings to supplied conduit plate.
Customer provided
conduit fittings.
One or two AC input circuit breakers are provided (depending on module configuration).
Two ground studs (5/16” [M8]) are provided attached to the sides of the enclosure surrounding the AC input circuit breaker(s).
Recommended torque is 124 in-lbs (14 Nm) for AC input circuit breaker connection.
Recommended torque is 204-221 in-lbs (23-25 Nm) to grounding studs.
A
Feed
B
Feed
A
Feed
B
Feed
(optional)
(optional)
AC INPUT
380/480VAC, 3 Phase, 50/60Hz
AC INPUT
380/480VAC, 3 Phase, 50/60Hz
factory wiring
AC IN A
L1 L2 L3
AC IN B
L1 L2 L
3
factory wiring
L1 L2 L3
AC IN A
L1 L2 L3
AC
IN B
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
GND
Stud
GND
Stud
GND
Stud
GND
Stud