User Instructions UM582127000
Spec. No. 582127000 (Model 721NPBB) Issue AC, January 2, 2013
Chapter 4. Troubleshooting and Repair Page 57
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-18
Replacing a Battery Disconnect Contactor
in a 1-Row Distribution Cabinet
Battery
Disconnect
Contactor
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Components removed in
illustration for clarity only.
Contactor styles vary
between manufacturer’s.
Front
5/16-18 x 1” Bolt
5/16" Belleville Lock Washer
5/16" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
5/16" Hardened Flat Washer
(4 places)
Torque to 100 in-lbs.
White/Black Wire
Brown Wire
Brown/White Wire
Red/White Wire
Brown Wire
Brown/White Wire White/Black Wire
Red/White Wire