Reference manual Foundation Fieldbus Control module
DOC.RM.QC34.E Rev: A
October, 2006
Index
No.
Name Description Valid Range Initial Value Permission
33 ZERO_PWR_COND The position where the valve will move to when no
power is present (airpressure should be present for DA)
closed, open
closed, open closed Read only
34 BUTTONBOARD_ENABLE Enables and disables the buttonboard for initialization. Set
to default will always be possible.
Can only be enable when in OOS. When not in OOS it
automatcally returns to false, to come back to its original
setting when in OOS. FF card must change this setting
on the sensorboard.
- enable when
in OOS
- Never in OOS
enable when in
OOS
Read / Write
36 FM_COUNTER Counts the end position cycles performed by the control
module.
FM_CNT_VALUE (read only) 0 - 4294967295 N/A Read only
FM_CNT_LIMIT [2] 0 -
4294967295
1,000,000 Read / Write
37 PM_COUNTER Counts the end position cycles performed by the
pneumatic module
PM_CNT_VALUE 0 - 4294967295 N/A Read / Write
PM_CNT_LIMIT [2] 0 -
4294967295
1,000,000 Read / Write
38 ACT_COUNTER Counts the end position cycles performed by the actuator
ACT_CNT_VALUE 0 - 4294967295 N/A Read / Write
ACT_CNT_LIMIT [2] 0 -
4294967295
1,000,000 Read / Write
39 VALVE_COUNTER Counts the end position cycles performed by the valve
VLV_CNT_VALUE 0 - 4294967295 N/A Read / Write
VLV_CNT_LIMIT [2] 0 -
4294967295
1,000,000 Read / Write
40 TIMERS (units are seconds). TIME_IN_POSITION - Holds the time in current position
Reset to zero when power switched off
0 to
4294967295
0 Read only
TIME_IN_POSITION_HI_LIM - Sets a limit for an alert for
the time in position
[2] 0 to
4294967295
0 read.write
OPEN_TIMERAVEL_TIME Indicates time between:
- Pilot position change commanded and
- Open trip position reached.
0 to 65536 0 Read only
OPEN_TRAVEL_TIME_HI_LIM [2] 0 to 65536 0 Read / Write
OPEN_TRAVEL_TIME_LO_LIM [2] 0 to 65536 0 Read / Write
OPEN_TRAVEL_TIME_AVG (average of 30 strokes) 0 to 65536 0 Read only
OPEN_TRAVEL_AVG_HI_LIM [2] 0 to 65536 0 Read / Write
OPEN_TRAVEL_AVG_LO_LIM [2] 0 to 65536 0 Read / Write
CLOSE_TRAVEL_T Indicates time between:
- Pilot position change commanded and
- Close trip position reached.
0 to 65536 0 Read only
CLOSE_TRAVEL_TIME_HI_LIM [2] 0 to 65536 0 Read / Write
CLOSE_TRAVEL_TIME_LO_LIM [2] 0 to 65536 0 Read / Write
CLOSE_TRAVEL_TIME_AVG (average of 30 strokes) 0 to 65536 0 Read only
CLOSE_TRAVEL_AVG_HI_LIM [2] 0 to 65536 0 Read / Write
CLOSE_TRAVEL_AVG_LO_LIM [2] 0 to 65536 0 Read / Write
Table 4.2 FieldQ™ Transducer Block (continued)
Diagnostic configuration
Device configuration (continued)