161
Monitor display and monitor output signal
4
PARAMETERS
4.12.5 How to calibrate the terminal FM when using the operation panel (FR-DU07)
Perform the following procedure to calibrate terminal FM using the operation panel FR-DU07. Refer to page 159 for
the details of parameters.
REMARKS
⋅ Calibration can also be made for external operation. Set the frequency in External operation mode, and make calibration in
the above procedure.
⋅ Calibration is available even during operation.
⋅ For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
♦ Parameters referred to ♦
C0(Pr.900) FM terminal calibration Refer to page 159
C1(Pr.901) AM terminal calibration Refer to page 159
Press to return to the indication (step 8).
13. Press . Setting is complete.
2. Press to choose the parameter
setting mode.
3.
Flicker...Parameter setting complete!!
Flicker...Parameter setting complete!!
Analog indicator
6. Press to set.
7.
5.
" ".
4. Press to read the present set value.
" " (initial value) appears.
1.Confirmation of the RUN indicator and
operation mode indicator
8. Press to display .
10. Press to enable setting.
11. If the inverter is at a stop, (press
or ) to start the inverter.
(Motor needs not be connected.)
12. Turn to adjust the indicator needle
to the desired position.
( ) )
By turning , you can read another parameter.
+
-
The parameter
number read
previously appears.
(When Pr. 54=1)
Press twice to show the next parameter ( ).
Display
Operation
9.
C0 FM terminal calibration
.
C0 to C7
setting
is enabled.
The monitor set to Pr. 54 FM terminal
function selection is displayed.