E6581381
F-17
6
[Parameter setting]
Title Function Adjustment range Default setting
H
VIA input point 1 setting 0-100 (%) 0
H
VIA input point 1 frequency 0.0-200.0 (Hz) 0.0
H
VIA input point 2 setting 0-100 (%) 100
H
VIA input point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
H
VIB input point 1 setting 0-100 (%) 0
H
VIB input point 1 frequency 0.0-200.0 (Hz) 0.0
H
VIB input point 2 setting 0-100 (%) 100
H
VIB input point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
H
Communication command point 1 setting 0-100 (%) 0
H
Communication command point 1 frequency 0.0-200.0 (Hz) 0.0
H
Communication command point 2 setting 0-100 (%) 100
H
Communication command point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
Note: Don't set the same value between point 1 and point 2. If set the same falue, the GTT is displayed.
1) 0-10Vdc voltage input adjustment (VIA, VIB)
IA, VIB terminals
The output frequenc
with
respect to the voltage input is
adjusted according to the
selected reference point.
Gradient and bias can be set
easily.
H H
100 (%)
10V voltage signal
H H
0 ( Hz)
H H
0 (%)
H H
60 ( Hz )
0
Output
frequency
Frequenc
commnd
2) 4-20mAdc current input adjustment (VIA: VIA (SW3) slide switch in the I position)
IA terminal
The output frequency with respect to
the current input is adjusted
according to the selected reference
point.
Gradient and bias can be set easily.
Set
H
to
to create a current
input from 0 to 20mA.
H
100 (%)
20mA current signal
H
0 ( Hz)
H
20 (%)
4
H
60 ( Hz )
Output
frequency
Frequency commnd