CHAPTER 2: POWER REQUIREMENTS
12
Burst Current — The maximum rms current during a
period of around one second. The Burst Current is used
as a rating for magnetic breakers. It is also used for cal-
culating the peak voltage drop in long AC cable runs
according to the following formula:
V pk (drop) = I pk x R (cable total)
The Burst Current can also be used to calculate the AC
looping capability of Acheron Designer.
Ultimate Short-Term Peak Current — A rating for fast-
reacting magnetic breakers.
Inrush Current — The spike of initial current encoun-
tered when powering on.
You can use Table 2 as a guideline for selecting cable
gauges and circuit breaker ratings for the system’s operat-
ing voltage.
The minimum electrical service amperage required by an
Acheron Designer loudspeaker system is the sum of the
Maximum Long-Term Continuous Current for each loud-
speaker. An additional 30 percent above the minimum
amperage is recommended to prevent peak voltage drops at
the service entry.
NOTE: For best performance, the AC cable
voltage drop should not exceed 10 V, or
10 percent at 115 V and 5 percent at 230 V. Make
sure that even with AC voltage drops that the AC
voltage always remains within the operating win-
dows.
ELECTRICAL SAFETY GUIDELINES
Pay close attention to these important electrical and safety
guidelines.
The Acheron Designer requires a grounded outlet.
Always use a grounded outlet and plug.
Do not use a ground-lifting adapter or cut the AC cable
ground pin.
Do not exceed the current capability of the 20-amp AC
Input connector for the loudspeaker. When looping loud-
speakers, consider the total current draw for all loud-
speakers on the circuit, including the first loudspeaker.
Make sure the AC power cable for the loudspeaker has
the appropriate power plug (on the other end) for the
area in which you will operate the loudspeaker. In addi-
tion, the AC power cable must be rated for the total cur-
rent draw of all loudspeakers looped from the power
source.
Do not operate the unit if its power cable is frayed or bro-
ken.
Keep all liquids away from the Acheron Designer to avoid
hazards from electrical shock.
Table 2: Acheron Designer Current Draw
Current Draw 115 V AC 230 V AC 100 V AC
Idle Current 0.23 A rms 0.19 A rms 0.24 A rms
Maximum Long-Term
Continuous Current
1.58 A rms 0.83 A rms 1.78 A rms
Burst Current 3.1 A rms 1.4 A rms 3.6 A rms
Ultimate Short-Term
Peak Current
12.0 A peak 8.0 A peak 12.4 A peak
Inrush Current 25 A peak 54 A peak 20 A peak
Earth ground
Chassis ground