Sanyo UH2442 / CH2442 Car Speaker User Manual


 
I - 108
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: XH3642 / Outdoor model: CH3642
Cooling
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.9 - 0.8 1.8 - 1.8 12.7 - 13.2 15.4 - 15.8
kW 0.20 - 0.16 0.36 - 0.34 2.79 - 2.70 3.35 - 3.20
Full load conditions
A 0.9 - 0.8 1.8 - 1.8 15.4 - 16.7 18.1 - 19.3
kW 0.20 - 0.16 0.36 - 0.34 3.43 - 3.41 3.99 - 3.91
Starting amperes A 1 - 1 2 - 2 95 - 86 98 - 89
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.7 - 0.6 1.8 - 1.8 15.7 - 16.9 18.2 - 19.3
kW 0.16 - 0.12 0.36 - 0.34 3.33 - 3.29 3.85 - 3.75
Full load conditions
A 0.7 - 0.6 1.8 - 1.8 14.2 - 15.6 16.7 - 18.0
kW 0.16 - 0.12 0.36 - 0.34 3.16 - 3.21 3.68 - 3.67
Starting amperes A 1 - 1 2 - 2 95 - 86 98 - 89