Sanyo UH2442 / CH2442 Car Speaker User Manual


 
I - 114
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: UH3642 / Outdoor model: CH3642
Cooling
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 1 - 1 1.8 - 1.8 12.3 - 13.7 15.1 - 15.7
kW 0.22 - 0.2 0.36 - 0.34 2.77 - 2.63 3.35 - 3.17
Full load conditions
A 1 - 1 1.8 - 1.8 15.4 - 16.8 18.2 - 19.6
kW 0.22 - 0.2 0.36 - 0.34 3.45 - 3.38 4.03 - 3.92
Starting amperes A 2 - 2 2 - 2 95 - 86 98 - 89
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.9 - 0.8 1.8 - 1.8 15.5 - 17 18.2 - 19.6
kW 0.21 - 0.18 0.36 - 0.34 3.21 - 3.24 3.78 - 3.76
Full load conditions
A 0.9 - 0.8 1.8 - 1.8 14.7 - 16 17.4 - 18.6
kW 0.21 - 0.18 0.36 - 0.34 3.32 - 3.29 3.89 - 3.81
Starting amperes A 2 - 2 2 - 2 95 - 86 97.9 - 88.8