Sanyo XH4242 / CH4242 Car Speaker User Manual


 
I - 115
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: KH2442 / Outdoor model: CH2442
Cooling
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.4 - 0.4 0.9 - 0.9 9.0 - 9.6 10.3 - 10.9
kW 0.08 - 0.07 0.18 - 0.17 2.04 - 1.98 2.30 - 2.22
Full load conditions
A 0.4 - 0.4 0.9 - 0.9 11.0 - 11.7 12.3 - 13.0
kW 0.08 - 0.07 0.18 - 0.17 2.46 - 2.44 2.72 - 2.68
Starting amperes A 1 - 1 1 - 1 66 - 60 68 - 62
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.4 - 0.4 0.9 - 0.9 10.0 - 10.9 11.3 - 12.2
kW 0.08 - 0.07 0.18 - 0.17 2.24 - 2.19 2.50 - 2.43
Full load conditions
A 0.4 - 0.4 0.9 - 0.9 11.1 - 11.7 12.4 - 13.0
kW 0.08 - 0.07 0.18 - 0.17 2.52 - 2.44 2.78 - 2.68
Starting amperes A 1 - 1 1 - 1 66 - 60 68 - 62