Sanyo XH2442 / CH2442 Car Speaker User Manual


 
I - 110
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: TH2442 / Outdoor model: CH2442
Cooling
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.4 - 0.4 0.9 - 0.9 10.4 - 11.6 11.7 - 12.9
kW 0.08 - 0.07 0.18 - 0.17 2.29 - 2.26 2.55 - 2.50
Full load conditions
A 0.4 - 0.4 0.9 - 0.9 11.4 - 11.8 12.7 - 13.1
kW 0.08 - 0.07 0.18 - 0.17 2.55 - 2.44 2.81 - 2.68
Starting amperes A 1 - 1 1 - 1 66 - 60 68 - 62
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.4 - 0.4 0.9 - 0.9 9.4 - 10.0 10.7 - 11.3
kW 0.08 - 0.07 0.18 - 0.17 2.09 - 2.04 2.35 - 2.28
Full load conditions
A 0.4 - 0.4 0.9 - 0.9 11.0 - 11.7 12.3 - 13.0
kW 0.08 - 0.07 0.18 - 0.17 2.45 - 2.42 2.71 - 2.66
Starting amperes A 1 - 1 1 - 1 66 - 60 68 - 62