CGs-4E Gas-Fired Water Boiler — Boiler Manual
Start-up — operate boiler (continued)7b
Figure 16 Typical pilot burner flame
Figure 17 Typical main burner flame
Check burner flames
ViewpilotandmainamesthroughtheinspectionportintheAirinlet
box front cover.
Pilot burner flame (Figure 16)
PROPER pilot flame characteristics
1. Blueame.
2. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.
IMPROPER pilot flame characteristics:
1. Overfired — Large flame lifting or blowing past pilot flame sensor.
2. Underred—Smallame.Innerconenotengulngpilotamesen-
sor.
3. Lackofprimaryair—Yellowametip.
4. Incorrectly heated pilot flame sensor.
Main burner flame (Figure 17)
PROPER main burner flame characteristics
1. Yellow-orangestreaksmayappear(causedbydust).
(NOTE:TheCGs-4Ewilloperateatlowrefortherst60seconds.)
IMPROPER main burner flame characteristics
1. Overfired — Large flames.
2. Underred—Smallames.
3. Lackofprimaryair—Yellowtippingonames(sootingwilloccur).
If you discover evidence of any gas leak, shut down the
boiler at once. Find the leak source with bubble test and
repairimmediately.Donotstartboileragainuntilcor-
rected. Failure to comply could result in severe personal
injury, death or substantial property damage.