Troubleshooting
4–6 152379 Rev C
0021 PV Over-Voltage S This fault indicates that the PV100S
has detected a DC input voltage of
greater than the maximum allowed
value of 600 Vdc.
PV system wiring short
Lightning strike on PV
system wiring
0023 Bus Voltage High H This fault indicates that the PV100S
has detected that the DC bus voltage
has exceeded the maximum allowed
value of 925 Vdc.
PV system wiring short
Lightning strike on PV
system wiring
XX30 Matrix Over Current S This fault indicates that the PV100S
has detected that the AC current on
one or more phases of the inverter
output has exceeded the maximum
allowed value of 712 A
rms
.
The first two digits of the fault code
indicate the particular phase where
the over current occurred as follow:
0130 - Matrix over current in
phase A
0230 - Matrix over current in
phase B
0430 - Matrix over current in
phase C
If more than one phase faults
simultaneously, the two first digits
are added in hexadecimal form to
indicate an over current condition in
more than one phase, thus the error
code will contain the summation of
the faulted phases.
CT1 or CT2 are
inoperable
CCU2 ±15Vdc Power
Supply is defective
P3 on CCU2 is loose or
disconnected
AC system wiring short
0033 Ground Over
Current
S This fault indicates that the PV100S
has detected that the ground fault
current has exceeded the maximum
allowed value. This maximum
allowed value for ground fault current
is a user-configurable setting with a
range of 1 to 20 Adc. The default
setting for this value is 10 Adc.
CT3 is inoperable
CCU2 ±15 Vdc Power
Supply is defective
P3 on CCU2 is loose or
disconnected
Ground -to-AC or
DC-to-System wiring
short
Table 4-1
Fault Codes
Error
Code Fault Source(s)
Fault Type
H=Hardware
S=Software
Fault Description Possible Causes