1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: KH3642 / Outdoor model: CH3642
● Cooling
● Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.5 - 0.5 1.8 - 1.8 12.6 - 13.2 14.9 - 15.5
kW 0.10 - 0.09 0.36 - 0.34 2.83 - 2.69 3.29 - 3.12
Full load conditions
A 0.5 - 0.5 1.8 - 1.8 15.4 - 16.8 17.7 - 19.1
kW 0.10 - 0.09 0.36 - 0.34 3.45 - 3.38 3.91 - 3.81
Starting amperes A 1 - 1 2 - 2 95 - 86 97.5 - 88.5
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.5 - 0.5 1.8 - 1.8 15.5 - 16.8 17.8 - 19.1
kW 0.10 - 0.09 0.36 - 0.34 3.40 - 3.38 3.86 - 3.81
Full load conditions
A 0.5 - 0.5 1.8 - 1.8 14.7 - 16.0 17 - 18.3
kW 0.10 - 0.09 0.36 - 0.34 3.32 - 3.29 3.78 - 3.72
Starting amperes A 1 - 1 2 - 2 95 - 86 97.5 - 88.5