4. Service procedures
(2) Checking the Protective Devices
• Disconnect the connector, which consists of P (plug) and S (socket) when you want to
check the protective device.
• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. IV-18.
• Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
11
11
1 Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
• Disconnect the connector which leads to the indoor fan motor (FMI).
• Check the socket’s terminals.
22
22
2 Compressor motor thermal protector . . . . . . Outdoor unit
• Disconnect the wires from terminals of compressor.
• Check the terminals of compressor.
33
33
3 Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
• Disconnect both the connector which leads to the outdoor fan motor (FMO).
• Check socket’s terminal.
Ω
socket
Multimeter
0642_X_S