139 95-7769—01
Fan Speed nvoData1 FanSpeed NumericPoint
Fan Switch nvoData1 FanSwitch EnumPoint
Filter Pressure nvoData2 FilterPressure NumericPoint
Free State 1 nvoData1 Free1Stat EnumPoint
Heat Source nvoData1 HeatSource EnumPoint
Heat Stages On nvoData1 HeatStagesOn NumericPoint
Heating Percentage nvoData1 HeatPos NumericPoint
Indoor Air Quality Override nvoData1 IaqOverRide EnumPoint
Manual Occupancy nvoData1 NetManOcc EnumPoint
Mixed Air Temperature nvoData2 MixedTemp NumericPoint
Mode nvoData1 mode EnumPoint
Monitor 1 nvoData2 Monitor1 NumericPoint
Monitor Switch nvoData1 MonSwitch EnumPoint
Occupancy Statue Out nvoData1 OccStatusOut EnumPoint
Occupancy Time Clock nvoData1 OccTimeClock EnumPoint
Outdoor Air Enthalpy nvoData2 OutdoorEnthalpy NumericPoint
Outdoor Humidity nvoData2 OutdoorHumidity NumericPoint
Outdoor Temperature nvoData2 OutdoorTemp NumericPoint
Outside Air Quality nvoData2 OutsideQuality NumericPoint
Override nvoData1 OverRide EnumPoint
Proof Of Air Flow nvoData1 ProofAirFlow EnumPoint
Return Air Enthalpy nvoData2 ReturnEnthalpy NumericPoint
Return Air Humidity nvoData2 ReturnHumidity NumericPoint
Return Air Temperature nvoData2 ReturnTemp NumericPoint
Scheduled Occupancy nvoData1 SchedOcc EnumPoint
Sensor Occupancy nvoData1 SenOcc EnumPoint
Shutdown nvoData1 ShutDown EnumPoint
Smoke Monitor nvoData1 SmokeMonitor EnumPoint
Space CO2 nvoData2 SpaceCo2 NumericPoint
Space Temperature nvoData2 SpaceTemp NumericPoint
Temperature Setpoint nvoData2 TempControlPt NumericPoint
Window Open nvoData1 WindowOpen EnumPoint
Table 84. UV Point Details. (Continued)
Point Name Network Variable Field Name Point Type
Table 85. UV Application of Points.
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values
Occupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0