Lamp Start-Up Timing
Diagram for Remote Input
Contact Closures
The Off/Reset contact must be closed for the unit to
go to Standby or On. Once the lamphead is put
into the Standby or On mode the lamphead will
remain in that mode until the Off/Reset contact is
opened.
1500003A
Lamp Off Lamp to Standby Lamp to ON Lamp Off
1
0
1
0
1
0
LAMP ON
STANDBY
OFF/RESET
>100 ms pulse
10 seconds to warm up
8 seconds to stabilize
>100 ms pulse
Figure 4-2 Lamp Start Up Timing Diagram for Remote Input Contact Closures