R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
14
Ignition Trials
60 secondsM4A closes; power is applied to terminals
18, 5, and 6, energizing the ignition transformer and
pilot valve (or main fuel valve(s) on terminal 7 if using
direct spark ignition).
When a flame is detected, relay 2K pulls in, 2K2
opens, and the LS HTR stops heating; 2K1 and
2K3 close.
65 secondsM9B opens; 5 second ignition (terminal 18)
is de-energizes (pilot only until 70 seconds).
66 secondsM3A closes, bypassing the low fire switch
and the timer switch.
70 secondsM2B opens; pilot or ignition trial ends; a
flame must be detected by this time (2K pulled in and
2K1 closed) or safety shutdown occurs and the lockout
switch trips.
M2A closes; power is applied to terminal 7,
energizing the main fuel valve(s).
M11B opens; prevents 2K from pulling in after this
time.
80 secondsM6B opens; 10 second interrupted pilot/
ignition (terminal 5) de-energizes.
100 secondsM4A opens; 30 second interrupted pilot/
ignition (terminal 6) de-energizes.
M8A closes, M8B opens; firing rate motor is
released to modulate under control of the
Series 90 Controller.
104 secondsM5B opens; timer stops with the system in
the run condition.
Run Period (Burner is Firing)
Postpurge and Stop
104 secondsWhen the operating setpoint is reached, the
burner controller contacts open; relay 1K and the main
fuel valve(s) (terminal 7) de-energize.
1K2 closes; timer motor starts; postpurge begins.
When the flame goes out, relay 2K drops out.
112 secondsM8A opens; firing rate motor stops
modulating under control of the Series 90 Controller.
116 secondsM8B closes; firing rate motor drives toward
low fire position (closed).
120 secondsM1B opens; timer and burner motor stop;
cycle ends.
Fig. 9 shows all contacts in the standby position (zero
seconds). The opening and closing times are shown adjacent
to each timer contact. Refer to Fig. 10 and the Step-by-Step
Operation section.