R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
5
Accessories:
W136A Test Meter (includes 117053 Meter Connector
Plug); has SPL position with damping for testing self-
checking flame detection systems.
117053 Meter Connector Plug (for older W136A models).
123514A Flame Simulator (for use with R7247A
Rectification Amplifiers).
123514B Flame Simulator (for use with R7249A Ultraviolet
Amplifiers).
139695C (Series 1 and 2) Cover with reset button; heavy
duty, metal cover for outside panel mounting.
202050C (Series 3) Cover with reset button; heavy duty,
metal cover for outside panel mounting.
118760B (Series 1 and 2) Remote Reset Cover; heavy
duty, metal cover with remote reset assembly; 120V,
60 Hz solenoid.
202051B (Series 3) Remote Reset Cover; heavy duty,
metal cover with remote reset assembly; 120V, 60 Hz
solenoid.
R1061012 Ignition Cable; for ignition installations in a high
temperature environment; rated at 350°F (177°C) for
continuous duty, and up to 500°F (260°C) for
intermittent use; tested to 25,000V.
R1298020 Cable; for flame detector (F lead-wire)
installations in a high temperature environment; rated
up to 400°F (204°C) for continuous duty; tested for
operation up to 600V and breakdown up to 7500V.
R1239001 High Tension Ignition Cable; for ignition
installations in a contaminating environment; very
resistant to severe conditions of oil, heat, and corona,
and tested to withstand high voltages up to
25,000V rms in a salt bath for one minute without
breakdown; rated at 200°F (93°C) for continuous duty,
and up to 350°F (197°C) for intermittent use.
Q624A Solid State Spark Generator; prevents detection of
ignition spark when properly applied with flame
detection systems using C7027, C7035, or C7044
Minipeeper Ultraviolet Flame Detectors. For use only
with gas pilots.
FSP5004 Tester; provides a quick operational check of
most R4140 Flame Safeguard Programming Controls.
Q520E1002 Service Tool; allows any of the programmer
terminals to be monitored while the programmer is
operating.
Plug-In Flame Signal Amplifiers Applicable Flame Detectors
Type Color
Self-
Checking Model
Flame Failure
Response Time Fuel Type Models
Rectification Green No R7247A 2 to 4 sec Gas Rectifying
Flame Rods
Holders
a
: C7004, C7007, C7011.
Complete assemblies: C7005,
C7008, C7009, Q179.
R7247A,
R7247B
b
2 to 4 sec Oil Rectifying
Photocells
c
C7003, C7010, C7013, C7014.
Gas,
Oil,
Coal
Ultraviolet
(Purple
Peeper)
C7012A or C.
Dynamic
Self-
Check
R7147B
b
2 to 4 sec Gas Rectifying
Flame Rods
Holders
a
: C7004, C7007, C7011.
Complete Assemblies: C7005,
C7008, C7009, Q179.
R7247C
d
2 to 4 sec Gas,
Oil,
Coal
Ultraviolet
(Purple
Peeper)
C7012E or F
Infrared Red No R7248A 2 to 4 sec Gas,
Oil,
Coal
Infrared
(Lead
Sulfide)
C7015.
Dynamic
Ampli-
Check®
R7248B
b
2 to 4 sec Gas,
Oil,
Coal
Infrared
(Lead
Sulfide)
C7015.
Ultraviolet Purple No R7249A 2 to 4 sec Gas,
Oil
Ultraviolet
(Minipeeper)
C7027, C7035, C7044.
Blue Dynamic
Self-
Check
R7476A
d
2 to 4 sec Gas,
Oil,
Coal
Ultraviolet
(Adjustable
Sensitivity)
C7076.
Table 4. Flame Detection Systems
NOTE: Neither the R414G1114 or the R4140G1122 can be used with the C7012E or F Purple Peeper Ultraviolet Flame
Detector and with the R7247C Dynamic Self-Check Amplifier.
a
Order flame rod separately; see Instructions for the holder.
b
Circuitry tests the flame signal amplifier at least 150 times a minute during burner operation and shuts down the burner if the
amplifier fails.
c
Use only Honeywell part no. 38316 Photocell.
d
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 60 to 240 times a minute during
burner operation and shuts down the burner if the detection system fails.