R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
18
Fig. 11. Simplified schematic diagram of R4140G1171, R4140G122 and R4140G1114 Programmers.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
B
R
W
B
R
W
14
12
11
10
9
L1
(HOT)
L2
1
2
120V, 60 HZ
POWER SUPPLY
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
A TIMER CONTACTS SNAP CLOSED.
B CONTACTS SNAP OPEN.
MASTER
SWITCH
L2
OOPENING TIME
CCLOSING TIME
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
INTERNAL
EXTERNAL
FLAME
DETECTOR
L1
PLUG-IN AMPLIFIER
FLAME SIGNAL
METER JACK
NUMBERS BELOW
DESIGNATE LINE
LOCATIONS OF
RELAY CONTACTS.
(UNDERLINE
INDICATES A
NORMALLY CLOSED
CONTACT.)
LS - 8, 22,
G
F
TIP JACK
17
16 4
8
13
3 9 13 5 8 12 10
1611
7
17
2K
1K
M11B
C-15 O-70
2K3
1K3
2K2
M7A
C-67 O-168
TO
TERMINAL
8
3
18
5
6
7
LIMITS
BURNER
CONTROLLER
START
INTERLOCK(S)
10 SECOND
INTERRUPTED
PILOT/IGNITION
30 OR 60 SECOND
INTERRUPTED
PILOT/IGNITION
RUNNING INTERLOCKS
(INCLUDING AIRFLOW SWITCH)
MAIN FUEL
VALVES (S)
BURNER MOTOR
(BLOWER)
120V ALARM
HIGH FIRE
LOW FIRE
COMMON
MODULATE
M8B O-148 C-174
M8A C-148 O-168
M10B O-5 C-40
M10A C-5 O-34
1K - 12, 17, 17
M7B
O-13.5 C-174
LS HTR
LS2
M2B
O-80
C-169
2K1
M4A
C-70
O-110
M12B
C-90
O-140
M9B
C-40 O-75
M2A C-80
O-163
M6B
C-60 O-90
1K1 1K2
M1B
C-6
O-180
M3A
O-60 C-76
LOW FIRE
SWITCH
NORM
TEST
TIMER SWITCH
M5B
O-155
C-164
TIMER MOTOR
FIRING
RATE
MOTOR
SERIES 90
CONTROLLER
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR
F OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE
BLOCK DIAGRAM OF FIELD WIRING.
TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.
A JUMPER IS INSTALLED ON THE BACK OF THE PROGRAMMER TO OBTAIN 60
SECOND INTERRUPTED PILOT/IGNITION AT TERMINAL 6; WITHOUT JUMPER,
IT IS 30 SECONDS.
FOR DIRECT SPARK IGNITION OF OIL, A JUMPER IS INSTALLED BETWEEN
TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM OF FIELD WIRING FOR
HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.
SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR
OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S).
TIMER SWITCH IS SHOWN IN NORM POSITION; IT IS OPEN IN TEST POSITION.
USE A SERIES 90 MODULATING MOTOR.
M10158
LS1
9
6
5
7
1
2
3
4
5
6
7
9
8
8
5 SECOND
IGNITION
5
3 4
2K - 8, 10, 16