R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify order number. Order separately:
1. Flame detection system (amplifier and matching flame detector). See Table 4.
2. Q520A1089 or Q520A1121 Wiring Subbase.
3. Accessories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In CanadaHoneywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not match the listed specifications
exactly. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
MODELS:
R4140G Flame Safeguard Programming ControlsFlame
Safeguard protection and sequencing controls for use on gas,
oil, coal, or combination burners. See Table 1 for models
available.
Table 1. Models Available.
a
202050C Cover with reset button; heavy duty, metal cover for outside panel mounting.
b
Early spark termination available on terminal 18 (5 second ignition and 5 second pilot only).
c
If used for direct spark ignition (oil or gas), the flame-establishing period is 10 seconds.
Interlock Circuits:
Start Interlocks (R4140G1049, G1056, G1064, G1114,
G1122, G1148 and G1171)System controls must be
in proper positions or programmer will not start.
Preignition Interlocks (R4140G1007, G1015, and
G1106)Must be closed to start programmer. Prevent
ignition trials if interlocks open during prepurge; timer
recycles the programmer and system restarts if
condition is self-correcting.
Running Interlocks (all models)Must be closed (airflow
must be proven, fuel pressure must not be too low or
too high) within 9.5 seconds after startup or ignition
trials cannot be started. Running interlocks must remain
closed through the Run period or the automatic fuel
valves de-energize, the burner flame(s) goes out, and
the timer recycles the programmer.
Low Fire Interlock (all models)Timer stops at 52 seconds
until low fire proving switch closes, indicating damper is
closed prior to ignition.
Timer
Flame-Establishing
Period (sec)
Firing Rate
Model
With
Cover
a
Cycle
(sec)
Prepurge
(sec)
Early Spark
Termination
b
Pilot
c
Main Burner
(Field Selectable)
c
Postpurge
(sec)
Interlock
Circuits
Switching
Circuit
R4140G1007 Yes 120 60 No 10 10 or 30 16 Preignition,
R4140G1015 No Running
R4140G1106 No 120 60 No 10 10 or 15 16 (including
Airflow
Switch) and
Low Fire
4-wire
common,
R4140G1049 No 120 60 Yes 10 10 or 30 16 Start, high fire,
R4140G1056 Yes 120 60 Yes 10 10 or intermittent 16 Running low-fire,
R4140G1064 No 120 60 Yes 10 10 or intermittent 16 (including modulate)
R4140G1114 No 180 70 Yes 10 10, 30, or 60 25 Airflow
R4140G1122 No 180 70 Yes 10 10, 30 or 60 25 Switch) and
R4140G1148 No 120 60 Yes 10 10 or 15 16 Low Fire
R4140G1171 No 180 70 Yes 10 10 or 15 25