R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-23373
25
Fig. 16. Sample block diagram of field wiring for R4140G1049, R4140G1056, R4140G1064,
R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmers.
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR
INFRARED
(LEAD SULFIDE)
FLAME DETECTOR
C7027A, C7035A, OR
C7044A ULTRAVIOLET
FLAME DETECTOR
C7012A,C,E,F
OR C7076A
ULTRAVIOLET
FLAME DETECTOR
LOW FIRE
SWITCH
BURNER MOTOR
(BLOWER)
MAIN FUEL
VALVE(S)
10 SECOND
INTERRUPTED
PILOT/IGNITION
PILOT/IGNITION
IGNITION
TRANSFORMER
RUNNING
INTERLOCKS
(INCLUDING
AIRFLOW SWITCH)
START
INTERLOCK(S)
BURNER
CONTROLLER
ALARM
MASTER
SWITCH
120V, 60 HZ
POWER
SUPPLY
L1 (HOT)
L2
TO
1ST STAGE
FUEL VALVE
2ND STAGE FUEL
VALVE (OPTIONAL)
L2
5
6
7
FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERMITTENT
PILOT/IGNITION ON TERMINAL 6.
5
6
7
8
G
L1
L2
12
13
F
3
4
9
10
11
W
R
B
W
R
B
5 SECOND IGNITION
(EARLY SPARK
TERMINATION)
WIRING
SUBBASE
TERMINAL
STRIP (4)
LIMITS
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE ALL NEC CLASS 1 WIRING.
IF START INTERLOCK(S) IS NOT USED, INSTALL A JUMPER
BETWEEN TERMINALS 4 AND 16.
5 SECOND IGNITION IS AVAILABLE ONLY ON THE R4140G1049,
G1056, G1064, G1114, G1122, G1148, AND G1171 MODELS.
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. ON R4140G114,
G1122, G1171 FOR 60 SECOND INTERRUPTED PILOT IGNITION, INSTALL
JUMPER (IN 4074B2V BAG ASSEMBLY) ON BACK OF PROGRAMMER
BETWEEN SCREW TERMINALS LABELED "JUMPER TO EXTEND MAIN
IGNITION TRIAL."
30 SECOND INTERRUPTED PILOT/IGNITION (30 SECOND MAIN BURNER
FLAME-ESTABLISHING PERIOD, MBFEP) ON THE R4140 AND
R4140G1049, G1114, G1122, G1171, 15 SECOND INTERRUPTED PILOT/
IGNITION (15 SECOND MBFEP) ON THE R4140G1148. INTERMITTENT
PILOT/IGNITION ON THE R4140G1056, AND R4140G1064.
FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE APPROPRIATE INSET.
1
1
2
2
3
4
5
6
3
4
5
6
7
8
9
10
11
12
L1
L2
L2
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION
60-2306 FOR DETAILED INSTRUCTIONS.)
C7012 OR C7076 MUST BE RATED FOR 120V, 60Hz. TWO DETECTORS
WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR
INSTRUCTIONS SEE FORM NUMBERS; 60-2046 FOR C7012A, C MODELS
WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON
TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR THE
C7076A.) C7012E,F UV FLAME DETECTORS WITH SELF CHECKING FEATURE
CANNOT BE USED WITH THE R4140G1122 OR R4140G1114.
WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER
ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A
ADJUSTABLE SENSITIVITY ULTRAVILOET FLAME DETECTOR DO NOT
HAVE LEADWIRES.
TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING
C7012E,F OR C7076A FLAME DETECTORS.
TERMINAL 16 IS USED ONLY AS A TIE POINT.
18
17
16
15
14
11
8
9
9
12
7
4
10
BLUE
BLUE
BLACK
BLACK
WHITE
WHITE
WHITE
YELLOW
OR
OR
M10059
IGNITION
TRANSFORMER
JUMPER
MAIN FUEL
VALVE (S)
TO
L2
5
6
7
FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERRUPTED
PILOT/IGNITION ON TERMINAL 6
HIGH FIRE
COMMON
MODULATE
LOW FIRE
SERIES 90
CONTROLLER
SERIES 90
FIRING RATE
MOTOR