Specifications
Dimensions
(H x W x D)
D6600 Rack mount (4U) 18 cm x 48.3 cm x 49.5 cm
(7.0 in x 19.0 in x 19.5 in)
Standalone 18 cm x 45.0 cm x 49.5 cm
(7.0 in x 17.75 i. x 19.5 in)
D6100IPv6 Rack mount (2U) 9.0 cm. x 37.5 cm. x 25.5 cm
(3.5 in x 19 in x 10 in)
Standalone 9.0 cm. x 30.5 cm. x 25.5 cm
(3.5 in x 12.0 in x 10 in)
Weight D6600 8.7 kg (19 lb)
D6100IPv6 3 kg (7 lb)
AC Nominal Operating
Range
120 V or 230 V
AC Maximum Operating
Range
100 VAC to 120 VAC, 220 VAC to 240 VAC, 50 - 60 Hz
2.5 A maximum
Power Cord IEC 60320 C13 type
Replaceable Fuse 2.5A F250V fast blow 5x20mm
D6100IPv6 Power Input AC Nominal Operating
Range
18VAC (see specific Installation Supplement supplied
with your product for your application for supplied
transformer specifics)
Current Required D6600 with one line card
installed
Required battery current 800 mA
Required UPS AC standby current 350 mA
For each additional line card
or terminal card pair
Required additional battery current 210 mA
Required additional UPS AC
standby current
35 mA
For network
communications card
Required additional battery current 10 mA
Required additional UPS AC
standby current
10 mA
D6100IPv6 Required battery current 330 mA
Required UPS AC standby current 250 mA
Standby Power The receiver includes an external battery connection and battery harness. Use 12 V
rechargeable sealed lead-acid batteries.
Standby power supply (UPS or battery) requirements: 24-hour minimum for UL Fire
applications (UL864); 4‑hour minimum for UL Burglary applications (UL1610).
Refer to Connecting External Batteries, page 27 for battery size.
Telephone RJ11C modular jacks, with 26 AWG or larger wire diameter.
17
80 en | Specifications
Conettix Communications Receiver/
Gateway