A SERVICE OF

logo

197
Communication operation and setting
4
PARAMETERS
Parameter
Faults history
Fault code list
Parameter Register Parameter Name
Read/
Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list (page
52) for the parameter names.
Read/write
The parameter number + 41000 is the register
number.
C2(902) 41902
Terminal 2 speed setting bias
(Speed)
Read/write
C3(902)
42092
Terminal 2 speed setting bias
(Analog value)
Read/write The analog value (%) set to C3 (902) is read.
43902
Terminal 2 speed setting bias
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
125(903) 41903
Terminal 2 speed setting gain
(Speed)
Read/write
C4(903)
42093
Terminal 2 speed setting gain
(Analog value)
Read/write The analog value (%) set to C4 (903) is read.
43903
Terminal 2 speed setting gain
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
C5(904) 41904
Terminal 4 speed setting bias
(Speed)
Read/write
C6(904)
42094
Terminal 4 speed setting bias
(Analog value)
Read/write The analog value (%) set to C6 (904) is read.
43904
Terminal 4 speed setting bias
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905) 41905
Terminal 4 speed setting gain
(Speed)
Read/write
C7(905)
42095
Terminal 4 speed setting gain
(Analog value)
Read/write The analog value (%) set to C7 (905) is read.
43905
Terminal 4 speed setting gain
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C42(934) 41934
PID display bias coefficient Read/write
C43(934)
42124
PID display bias analog value Read/write The analog value (%) set to C43 (934) is read.
43934
PID display bias analog value
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C44(935) 41935
PID display gain coefficient Read/write
C45(935)
42125
PID display gain analog value Read/write The analog value (%) set to C45 (935) is read.
43935
PID display gain analog value
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
Register Definition Read/write Remarks
40501 Fault history 1 Read/write
Being 2 bytes in length, the data is stored as
"H00".
Refer to the lowest 1 byte for the error code.
Performing write using the register 40501 batch-
clears the faults history.
Set any value as data.
40502 Fault history 2 Read
40503 Fault history 3 Read
40504 Fault history 4 Read
40505 Fault history 5 Read
40506 Fault history 6 Read
40507 Fault history 7 Read
40508 Fault history 8 Read
Data Definition
H00
No fault
present
H10 E.OC1
H11 E.OC2
H12 E.OC3
H20 E.OV1
H21 E.OV2
H22 E.OV3
H30 E.THT
H31 E.THM
H40 E.FIN
H52 E.ILF
H60 E.OLT
H61 E.SOT
H70 E.BE
H80 E.GF
H81 E.LF
H90 E.OHT
H91 E.PTC
HB0 E.PE
Data Definition
HB1 E.PUE
HB2 E.RET
HC0 E.CPU
HC4 E.CDO
HC5 E.IOH
HC7 E.AIE
HC9 E.SAF
HD0 E.OS
HE6 E.PID
HF5 E.5
Data Definition
* Refer to page 237 for details of fault description.