70
Test operation and gain adjustment of the PM sensorless vector control
(2) Valid/invalid statuses of I/O terminal functions during the test operation
1)Input terminal function selection (Pr. 178 to Pr. 182)
All assignable functions are valid.
2)Output terminal function selection (Pr. 190, Pr. 192)
Some functions have restrictions. For details, refer to the table below.
{: Valid, ×: Not output as there is no output current
(3) Valid/invalid statuses of monitor outputs during the test operation
{: Valid, ×: Invalid (always displays 0)
U: Displays accumulated value before the test, ⎯: Not monitored
Parameters referred to
Pr. 52 DU/PU main display data selection Refer to page 117
Pr. 190, Pr. 192 (Output terminal function selection) Refer to page 106
Signal
name
Function
RUN Drive unit running
SU Up to speed
OL Overload alarm ×
FU Rotation speed detection
RBP Regenerative brake pre-alarm
THP Electronic thermal O/L relay pre-alarm ×
RY Drive unit operation ready
Y12 Output current detection
Y13 Zero current detection
FDN PID lower limit
FUP PID upper limit
RL PID forward/reverse rotation output
MBR Electromagnetic brake interlock
FAN Fan fault output
FIN Heatsink overheat pre-alarm
RY2 Operation ready 2
PID During PID control activated
Y48 PID deviation limit
Y64 During retry
SLEEP PID output interruption
Y79 Pulse train output of output power ×
Y90 Life alarm
Y91 Fault output 3 (power-off signal)
Y92 Energy saving average value updated timing
Y93 Current average value monitor signal
Y95 Maintenance timer signal
REM Remote output
LF Alarm output
ALM Fault output
9999 No function ⎯
Signal
name
Function
*1 Monitor output is valid or invalid depending on the monitor type
(operation panel display, parameter unit display, or terminal FM/
AM). For details, refer to page 117.
*2 When the operation is switched to the test operation, "0" is
displayed. When the PM sensorless vector control is selected
again after a test operation, the following monitored items from the
last operation are displayed: output current peak value, motor
thermal load factor, drive unit thermal load factor, and the electronic
thermal relay load factor.
Monitoring items
operation
panel/PU
monitor
display
FM
output
Rotation speed
Output current ××
Output voltage ××
Fault display ⎯
Speed setting value
Converter output voltage
Regenerative brake duty
Electronic thermal relay load factor ×
*2 × *2
Output current peak value × *2 × *2
Converter output voltage peak value
Output power ××
Cumulative energization time ⎯
Reference voltage output ⎯
Actual operation time ⎯
Motor load factor ××
Cumulative power U ⎯
PID set point
PID measured value
PID deviation ⎯
Input terminal status ⎯/ ⎯
Output terminal status ⎯/ ⎯
Drive unit I/O terminal monitor /⎯⎯
Motor thermal load factor ×
*2 × *2
Drive unit thermal load factor × *2 × *2
PTC thermistor resistance ⎯
Monitoring items
operation
panel/PU
monitor
display
FM
output