64
27.3. Message Program Example
The programs shown in "Message Program/Sentence Composition Example" on the previous page operate as
follows.
(1) General-purpose broadcast message (Program No. 1)
[Continuous program playback method]
(2) Alert announcement message (Program No. 6)
[Repeat playback method]
(3) Evacuation announcement message (Program No. 7)
[Repeat playback method]
Step No.
001
Playback
002
003
004
Stop
Activation
Program P001
Silent interval 3 seconds
M003
1st sentence
A001
2nd sentence
A002
3rd sentence
A003
Returns to
step No. 001.
001
002
003
004
Step No.
Alert signal tone
A051
Program P006
Alert message
A052
Silent interval 1 second
M001
Silent interval 2 seconds
M002
Activation
Repeat interval: 0 second
(0, 10,
...
50 seconds,
1, 2,
...
99 minutes selectable)
Playback
Number of repeats: 5 times
(1, 2
...
128 times, Endless selectable)
Returns to
step No. 001.
001
002
003
004
Step No.
Evacuation signal tone
A061
Program P007
Evacuation message
A062
Silent interval 1 second
M001
Silent interval 2 seconds
M002
Activation
Repeat interval: 0 second
(0, 10,
...
50 seconds,
1, 2,
...
99 minutes selectable)
Playback
Number of repeats: Endless
(1, 2
...
128 times, Endless selectable)