Connections (continued)
Programming the foyer card reader MINITER RS 485
Programming is carried out using MINITER RS 485 software. This can be
installed on a service laptop or on a video system.
Proceed as follows:
1. Start the programming software and select RS 485 operation.
2. Select the COM port to which the foyer card readers are connected
via the “Interface” menu item.
Even if several foyer card readers MINITER RS 485 are to be pro-
grammed for the first time, only one foyer card reader should be con-
nected during programming. This is because the foyer card reader
will assign all the card readers with the same bus address by default.
3. Select the “MINITER → Read/Identify Miniter” menu and click “Iden-
tification of all activ addresses”.
“Address: 48” and “Protocol: Bosch” is displayed.
4. Select foyer card reader number 48 and confirm your selection with
”OK”.
5. Click “Read Miniter” and enter “Password: 991357”. Confirm with
”OK”.
6. The foyer card reader addresses must be specified as follows:
Foyer card reader no. 1 = address 48
Foyer card reader no. 2 = address 49
Foyer card reader no. 3 = address 50
Foyer card reader no. 4 = address 51
For operation, the other parameters must be set as follows:
– Door opening time: optional
– Door opener with buzzer: optional
– Door opener interval tone: optional
– Monitoring module: no
– Password: 991357
– Signal chipcard: no
– Send start character: no
– Data on display: no
– Evaluate track 2: yes
– Evaluate track 3 or 1: yes
– Open door on fault: no
– Protocol: Bosch
– Bloc list: optional
– Data length track 2: 18 (for credit cards)
– Data length track 3/1: 26 (for EC cards)