Mitsubishi Electronics MR-J2M-P8B Car Amplifier User Manual


 
5 - 16
5. PARAMETERS
(2) Details list
Classifi-
cation
No. Symbol Name and Function
Initial
Value
Unit
Setting
Range
0 *BPS Serial communication function selection, alarm history clear
Used to select the serial communication baudrate, select various
communication conditions, and clear the alarm history.
0
Serial baudrate selection
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid reset to "0".
Serial communication response delay time
0: Invalid
1: Valid, reply sent after delay time of 800 s or more
0000 Refer to
name
and
function
column.
01 SIC Serial communication time-out selection
Set the time-out period of the communication protocol in [s] unit.
Setting "0" disables time-out check.
0
s1
to
60
Basic IFU parameters
2 *OP1 Function selection 1
Used to select the protocol of serial communication.
00
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
0
0000 Refer to
name
and
function
column.