Mitsubishi Electronics MR-J2S- CP Car Amplifier User Manual


 
3 - 5
3. SIGNALS AND WIRING
3.3.2 Signal (devices) explanations
(1) I/O devices
POINT
The devices not indicated in the Connector Pin No. field of the I/O devices
can be assigned to the connector CN1A/CN1B using the MR Configurator
(servo configuration software).
(a) Pins whose devices can be changed
Refer to section 3.6.2 for the I/O interfaces (symbols in the I/O Division field in the table) of the
corresponding connector pins.
Pin type Connector pin No. I/O division Device in initial status
CN1B-5 Point table No. selection 1 (DI0)
CN1B-14 Point table No. selection 2 (DI1)
CN1A-8 Proximity dog (DOG)
CN1B-15 Servo-on (SON)
CN1B-16 Forward rotation stroke end (LSP)
CN1B-17 Reverse rotation stroke end (LSN)
CN1B-7 Automatic/manual selection (MD0)
CN1B-8 Forward rotation start (ST1)
Input-only pins
CN1B-9
DI-1
Reverse rotation start (ST2)
I/O pin CN1A-19 DI-1 or DO-1
No device has been assigned in the initial
status. You can assign an I/O device using
the MR Configurator (servo configuration
software).
CN1B-4 Rough match (CPO)
CN1B-6 Movement finish (MEND)
CN1B-18 Trouble (ALM)
CN1B-19 Ready (RD)
Output-only pins
CN1A-18
DO-1
Home position return completion(ZP)
(b) Input devices
Device name
Devices
symbol
Connector
pin No.
Functions/Applications
Forced stop EMG When EMG-SG are opened, the servo amplifier is placed in the forced stop status,
the servo switches off, and the dynamic brake is operated to bring the servo motor
to a sudden stop.
Short EMG-SG in the forced stop status to cancel the forced stop status.
Servo-on SON CN1B
15
Connect SON-SG to switch on the base circuit and make the servo amplifier ready
to operate (servo-on).
Disconnect SON-SG to shut off the base circuit and coast the servo motor (servo-
off) .
Reset RES Disconnect RES-SG for more than 50ms to reset the alarm.
Some alarms cannot be deactivated by the reset signal. Refer to section 11.2.1
If RES-SG are shorted in no alarm status, the base circuit is not shut off.
Set "
1 " in parameter No. 55 to shut off the base circuit.
Since this device is not designed for stopping. Do not switch it on during operation.