Mitsubishi Electronics MR-J3- T Car Amplifier User Manual


 
16 - 59
16. INDEXER POSITIONING OPERATION
(3) Operation
Turn on the start (RYn1) to operate the servo motor with the servo motor speed, acceleration time constant,
and deceleration time constant set in the point table No.1. Turning off RYn1 makes the servo motor
execute positioning to the station where the servo motor can decelerate to stop. For the rotation direction,
refer to (2) in this section.
(4) Timing chart
The following timing chart shows an example when executing the indexer JOG operation from the status
where the servo motor is at a stop on the station No.0 when the servo-on is turned on.
4ms or more 6ms or more
(Note 1)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
No.4 No.4
Parameter No.PA11, PA12
Parameter No.PC35
No.8
(Note 2)
4ms or more
Current station No.
No.0
0 1 2 3 4 5 6 7 8 7 6 5 484
Operation mode selection 2
(RYn7)
Operation mode selection 1
(RYn6)
Start (RYn1)
Rotation direction specifying
(RYn2)
Servo motor speed
Forward
rotation
Reverse
rotation
0r/min
In position (RXn1)
Station output 1 to 8
(RX(n 2)2 to RX(n 2)9)
(Note 1) (Note 1)
Parameter No.PC35Parameter No.PC35Parameter No.PC35
Parameter No.PA11, PA12Parameter No.PA11, PA12
Torque limit value to be effective
Out of in-position
range
Out of in-position
range
Out of in-position
range
Note 1. Torque limit delay time can be set in the parameter No.PD26.
2. The start (RYn1) is invalid even if it is turned on during operation. When executing another operation, turn on RYn1 after
the movement completion (RXnC) turns on.