Mitsubishi Electronics MR-J2M-P8A Car Amplifier User Manual


 
5 - 16
5. PARAMETERS
(2) Details list
Classifi-
cation
No. Symbol Name and Function
Initial
Value
Unit
Setting
Range
0 *BPS Serial communication function selection, alarm history clear
Used to select the serial communication baudrate function selection,
select various communication conditions, and clear the alarm
history.
Alarm history clear
0: Invalid
1: valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid (reset to 0).
Serial communication baudrate selection
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Serial communication I/F selection
0: RS-232C
1: RS-422
Communication response delay time selection
0: Invalid
1: valid, reply sent after time of 888 s or more
0000 Refer to
name
and
function
column.
1 *REG Regenerative brake option selection
Used to select the regenerative brake option.
00
Selection of regenerative brake option
00: Not used
01: Spare (do not set)
02: MR-RB032
05: MR-RB14
06: MR-RB34
07: MR-RB54
0000 Refer to
Name and
function
column.
Basic IFU parameters
2 *OP1 Function selection 1
Used to select the protocol of serial communication.
00
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
0
0000 Refer to
name
and
function
column.