14 - 52
14. OPTIONS AND AUXILIARY EQUIPMENT
2) 400V class
P
R2/L
1
S2/L
2
T2/L
3
R/L11
S/L
21
T/MC1
P/L+
N/L-
P
N
22mm
2
P
N
N
P
N
14mm
2
5.5mm
2
2mm
2
14mm
2
5.5mm
2
2mm
2
2mm
2
FR-CV-H55K
Servo amplifier (7kW)
Servo amplifier (3.5kW)
Servo amplifier (2kW)
Overall wiring length 5m or less
First unit:
22mm
2
assuming that the total of servo amplifier
capacities is 30kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
Junction terminals
Wire as short as possible.
Second unit:
14mm
2
assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
Third unit:
5.5mm
2
assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
Fourth unit:
2mm
2
assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
Servo amplifier (15kW)
(5) Other precautions
(a) Always use the FR-CVL-(H) as the power factor improving reactor. Do not use the FR-BAL or FR-BEL.
(b) The inputs/outputs (main circuits) of the FR-CV-(H) and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment
(such as AM radios) used near them. In this case, interference can be reduced by installing the
radio noise filter (FR-BIF-(H)) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV-(H) and servo
amplifiers should be 5m or less, and the wiring must be twisted.