Schneider Electric 4000 Car Video System User Manual


 
Chapter 6Alarms 63230-300-212
Alarm Conditions and Alarm Numbers April 2001
© 2001 Schneider Electric All Rights Reserved
94
Table 63: List of Default Alarms by Alarm Number
Alarm
Number
Alarm Description
Abbreviated
Display Name
Test
Register
Units
Scale
Group
Alarm
Type
Standard Speed Alarms (1 Second)
01 Over Current Phase A Over Ia 1100 Amperes A 010
02 Over Current Phase B Over Ib 1101 Amperes A 010
03 Over Current Phase C Over Ic 1102 Amperes A 010
04 Over Current Neutral Over In 1103 Amperes B 010
05 Over Current Ground Over Ig 1104 Amperes C 010
06 Under Current Phase A Under Ia 1100 Amperes A 020
07 Under Current Phase B Under Ib 1101 Amperes A 020
08 Under Current Phase C Under Ic 1102 Amperes A 020
09 Current Unbalance, Max I Unbal Max 1110 Tenths % 010
10 Current Loss Current Loss 3262 Amperes A 053
11 Over Voltage Phase AN Over Van 1124 Volts D 010
12 Over Voltage Phase BN Over Vbn 1125 Volts D 010
13 Over Voltage Phase CN Over Vcn 1126 Volts D 010
14 Over Voltage Phase AB Over Vab 1120 Volts D 010
15 Over Voltage Phase BC Over Vbc 1121 Volts D 010
16 Over Voltage Phase CA Over Vca 1122 Volts D 010
17 Under Voltage Phase A Under Van 1124 Volts D 020
18 Under Voltage Phase B Under Vbn 1125 Volts D 020
19 Under Voltage Phase C Under Vcn 1126 Volts D 020
20 Under Voltage Phase AB Under Vab 1120 Volts D 020
21 Under Voltage Phase BC Under Vbc 1121 Volts D 020
22 Under Voltage Phase CA Under Vca 1122 Volts D 020
23 Voltage Unbalance LN, Max V Unbal L-N Max 1136 Tenths % 010
24 Voltage Unbalance LL, Max V Unbal L-L Max 1132 Tenths % 010
25 Voltage Loss (loss of A,B,C, but not all) Voltage Loss 3262 Volts D 052
26 Phase Reversal Phase Rev 3228 ——051
27 Over kVA Demand Over kVA Dmd 2181 kVA F 011
28 Over kW Demand Over kW Dmd 2151 kW F 011
29 Over kVAR Demand Over kVAR Dmd 2166 kVAR F 011
30 Over Frequency Over Freq. 1180 Hundredths of Hertz 010
31 Under Frequency Under Freq. 1180 Hundredths of Hertz 020
32 Lagging true power factor Lag True PF 1163 Thousandths 055
33 Leading true power factor Lead True PF 1163 Thousandths 054
34 Lagging displacement power factor Lag Disp PF 1171 Thousandths 055
35 Leading displacement power factor Lead Disp PF 1171 Thousandths 054
36 Over Current Demand Phase A Over Ia Dmd 1961 Amperes A 010
37 Over Current Demand Phase B Over Ib Dmd 1971 Amperes A 010
38 Over Current Demand Phase C Over Ic Dmd 1981 Amperes A 010
39 Over THD Voltage ANOverTHDVan1207Tenths% 010
40 Over THD Voltage BNOverTHDVbn1208Tenths% 010
41 Over THD Voltage CNOverTHDVcn1209Tenths% 010
42 Over THD Voltage AB Over THD Vab 1211 Tenths % 010
Alarm Types are described in Table 64 on page 96.