Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup Menu April 2001
© 2001 Schneider Electric All Rights Reserved
20
Ta bl e 34 on page 20 describes the options on this menu.
4. Press the menu button until Save Changes? Noflashes on the display.
Select Yes with the arrow button, then press the enter button to save the
changes. Now, you are ready to set up the newly created custom alarm.
Table 3–4: Options for Creating an Alarm
Option Available Values Selection Description Default
Lbl Alphanumeric
Labelname of the alarm. Press the down arrow button to scroll through the alphabet. The lower
case letters are presented first, then uppercase, then numbers andsymbols. Press theenter button
to select a letter and move to the next character field. To move to the next option, press the menu
button.
Ty p e
Selectthetypeofalarmthatyouarecreating.
Note: For digital alarms, the type is either ON state, OFF state, or Unary to describe the state of the digital input. Unary
is available for digital alarms only.
Over Valover value
Over Pwrover power
Over Rev Pwrover reverse power
Under Valunder value
Under Pwrunder power
Phs Revphase reversal
Phs Loss Voltphase loss, voltage
Phs Loss Curphase loss, current
PF Leadleading power factor
PF Laglagging power factor
Binary
Time of Day
See Table 64 on page 96 for a description of alarm types.
Undefined
Qty
For standard or high speed alarms this is the quantity to be evaluated. While selected, press the arrow buttons to scroll
through the following quantity options: Current, Voltage, Demand, Unbalance, Frequency, Power Quality, THD,
Harmonics, Temperature, Custom, and Register. Pressing the enter key while an option is displayed will activate that
options list of values. Use the arrow keys to scroll through the list of options, selecting an option by pressing the enter key.
Undefined
Unary is a special type of alarm used for end ofdigital alarms. It does not apply to setting up alarms for digital inputs.
ALARM PARAMETERS
Lbl: Over THD Vbc
Type Over Val
Qty THD Vbc