Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup Menu April 2001
© 2001 Schneider Electric All Rights Reserved
36
Table 3–10: Options for Advanced Meter Setup
Option Available Values Selection Description Default
Phase Rotation ABC or CBA Set the phase rotation to match the system. ABC
Incr Energy Int 01440 Set incremental energy interval in minutes. The interval must be evenly divisible into
24 hours.
60
THD Meth THD(%Fund) or
thd(%RMS)
Set the calculation for total harmonic distortion. See Power Analysis Valueson page
66 for a detailed description.
THD
VARSign IEEE/IECor
ALT(CM1)
Set the VAR sign convention. See VAR Sign Conventions on page 55for a discussion
about VAR sign convention.
Standard
Lock Energy Reset Y or N Lock the reset of the accumulated energy. If set to Y (yes), the Energy option on the
Reset menu will be locked so that the value cannot be reset from the display, even if a
password has been setup forthe Reset option. See Resetting Min/Max, Demand, and
Energy Valueson page 37 for more information.
N
Lock Pk Dmd Reset Y or N Lock the reset of peak demand. If set to Y (yes), the Demand option on the Reset
menu will be locked so that the value cannot be reset from the display, even if a
password has been setup forthe Reset option. See Resetting Min/Max, Demand, and
Energy Valueson page 37 for more information.
N
Lock M/M Reset Y or N Lock the reset of the min/max values. If set to Y (yes), the Min/Maxoption on the Reset
menu will be locked so that the value cannot be reset from the display, even if a
password has been setup forthe Reset option. See Resetting Min/Max, Demand, and
Energy Valueson page 37 for more information.
N