63230-300-212 Appendix AAbbreviated Register Listing
April 2001 Register Listing
133
© 2001 Schneider Electric All Rights Reserved
1193 Auxiliary Analog Input Value, User-Selected Input 4
Refer to Analog Input
Setup
-32,767 to 32,767
1194 Auxiliary Analog Input Value, User-Selected Input 5
Refer to Analog Input
Setup
-32,767 to 32,767
1195 Auxiliary Analog Input Value, User-Selected Input 6
Refer to Analog Input
Setup
-32,767 to 32,767
1196 Auxiliary Analog Input Value, User-Selected Input 7
Refer to Analog Input
Setup
-32,767 to 32,767
1197 Auxiliary Analog Input Value, User-Selected Input 8
Refer to Analog Input
Setup
-32,767 to 32,767
1198 Auxiliary Analog Input Value, User-Selected Input 9
Refer to Analog Input
Setup
-32,767 to 32,767
1199 Auxiliary Analog Input Value, User-Selected Input 10
Refer to Analog Input
Setup
-32,767 to 32,767
Power Quality
1200 THD/thd Current, Phase A 0.10% 0 to 32,767
1201 THD/thd Current, Phase B 0.10% 0 to 32,767
1202 THD/thd Current, Phase C 0.10% 0 to 32,767
1203 THD/thd Current, Neutral 0.10% 0 to 32,767
1204 THD/thd Current, Ground 0.10% 0 to 32,767
1207 THD/thd Voltage, Phase A-N 0.10% 0 to 32,767
1208 THD/thd Voltage, Phase B-N 0.10% 0 to 32,767
1209 THD/thd Voltage, Phase C-N 0.10% 0 to 32,767
1210 THD/thd Voltage, Phase N-G 0.10% 0 to 32,767
1211 THD/thd Voltage, Phase A-B 0.10% 0 to 32,767
1212 THD/thd Voltage, Phase B-C 0.10% 0 to 32,767
1213 THD/thd Voltage, Phase C-A 0.10% 0 to 32,767
1218 K-Factor, Current, Phase A 0.10 0to10,000
1219 K-Factor, Current, Phase B 0.10 0to10,000
1220 K-Factor, Current, Phase C 0.10 0to10,000
1221 Crest Factor, Current, Phase A 0.01 0to10,000
1222 Crest Factor, Current, Phase B 0.01 0to10,000
1223 Crest Factor, Current, Phase C 0.01 0to10,000
1224 Crest Factor, Current, Neutral 0.01 0to10,000
1225 Crest Factor, Voltage, A-N/A-B 0.01 0to10,000
1226 Crest Factor, Voltage, B-N/B-C 0.01 0to10,000
1227 Crest Factor, Voltage, C-N/C-A 0.01 0to10,000
1230 Current Fundamental RMS Magnitude, Phase A A Amps/Scale 0 to 32,767
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registers on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.