1601 Maximum THD/thd Current, Phase B 0.10% 0 to 32,767
1602 Maximum THD/thd Current, Phase C 0.10% 0 to 32,767
1603 Maximum THD/thd Current, Phase N 0.10% 0 to 32,767
1604 Maximum THD/thd Current, Ground 0.10% 0 to 32,767
1607 Maximum THD/thd Voltage, Phase A-N 0.10% 0 to 32,767
1608 Maximum THD/thd Voltage, Phase B-N 0.10% 0 to 32,767
1609 Maximum THD/thd Voltage, Phase C-N 0.10% 0 to 32,767
1610 Maximum THD/thd Voltage, Phase N-G 0.10% 0 to 32,767
1611 Maximum THD/thd Voltage, Phase A-B 0.10% 0 to 32,767
1612 Maximum THD/thd Voltage, Phase B-C 0.10% 0 to 32,767
1613 Maximum THD/thd Voltage, Phase C-A 0.10% 0 to 32,767
1618 Maximum Current K-Factor, Phase A 0.10 0 to 10,000
1619 Maximum Current K-Factor, Phase B 0.10 0 to 10,000
1620 Maximum Current K-Factor, Phase C 0.10 0 to 10,000
1621 Maximum Crest Factor, Current, Phase A 0.01 0 to 10,000
1622 Maximum Crest Factor, Current, Phase B 0.01 0 to 10,000
1623 Maximum Crest Factor, Current, Phase C 0.01 0 to 10,000
1624 Maximum Crest Factor, Current, Neutral 0.01 0 to 10,000
1625 Maximum Crest Factor, Voltage A-N/A-B 0.01 0 to 10,000
1626 Maximum Crest Factor, Voltage B-N/B-C 0.01 0 to 10,000
1627 Maximum Crest Factor, Voltage C-N/C-A 0.01 0 to 10,000
1630 Maximum Current Fundamental RMS Magnitude, Phase A A Amps/Scale 0 to 32,767
1631 Maximum Current Fundamental Coincident Angle, Phase A 0.1 ° 0to3,599
1632 Maximum Current Fundamental RMS Magnitude, Phase B A Amps/Scale 0 to 32,767
1633 Maximum Current Fundamental Coincident Angle, Phase B 0.1 ° 0to3,599
1634 Maximum Current Fundamental RMS Magnitude, Phase C A Amps/Scale 0 to 32,767
1635 Maximum Current Fundamental Coincident Angle, Phase C 0.1 ° 0to3,599
1636 Maximum Current Fundamental RMS Magnitude, Neutral B Amps/Scale 0 to 32,767
1637 Maximum Current Fundamental Coincident Angle, Neutral 0.1 ° 0to3,599
1638 Maximum Current Fundamental RMS Magnitude, Ground C Amps/Scale 0 to 32,767
1639 Maximum Current Fundamental Coincident Angle, Ground 0.1 ° 0to3,599
1644 Maximum Voltage Fundamental RMS Magnitude, A-N/A-B D Volts/Scale 0 to 32,767
1645 Maximum Voltage Fundamental Coincident Angle, A-N/A-B 0.1 ° 0to3,599
1646 Maximum Voltage Fundamental RMS Magnitude, B-N/B-C D Volts/Scale 0 to 32,767
1647 Maximum Voltage Fundamental Coincident Angle, B-N/B-C 0.1 ° 0to3,599
1648 Maximum Voltage Fundamental RMS Magnitude, C-N/C-A D Volts/Scale 0 to 32,767
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to0; -0.999 maps to 0.999;0.999 leadingmaps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registerson page 187 for instructions on
howtousethesetup-modecommands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.