Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup Menu April 2001
© 2001 Schneider Electric All Rights Reserved
24
The I/O Extender Setup menu displays.
5. Select the Select Modules menu option.
The IOX Select Modules menu displays.
6. If you have the IOX-08, IOX-0404, or IOX-2411, select the option you
have installed. A pound sign (#) appears next to the option to indicate that
the circuit monitor has recognized the module. If you installed individual
custom I/Os, select Custom on the IOX Select Modules menu.
The Custom Extender menu displays.
7. Select the position in which the I/O is installed. Then, select which I/O
module is located in that position using the arrow keys to scroll through
the available I/Os. The individual I/Os are described in Table 36.
Table 3–6: I/O Descriptions
I/O Name Description
Digital I/Os
DI32DC 32 Vdc input (0.2ms turn on) polarized
DI120AC 120 Vac input
DO120AC 120 Vac output
DI240AC 240 Vac input
DO60DC 60 Vdc output
DO200DC 200 Vdc output
I/O EXTENDER SETUP
Select Modules
Configure Modules
IOX SELECT MODULES
IOX-08
IOX-0404
IOX-2411
Custom
CUSTOM
Position 1 DI120AC
Position 2 AI420
Position 3 DI120AC
Position 4 AI420
Position 5 DI120AC
Position 6 AI420
Position 7 DI120AC
Position 8 AI420