Chapter 4Metering Capabilities 63230-300-212
Power Analysis Values April 2001
© 2001 Schneider Electric All Rights Reserved
68
Table 45: Power Analysis Values
Value Reportable Range
THDVoltage, Current
3-phase, per-phase, neutral 0 to 3,276.7%
thdVoltage, Current
3-phase, per-phase, neutral 0 to 3,276.7%
Total Demand Distortion 0 to 10,000
K-Factor (per phase) 0.0to100.0
K-Factor Demand (per phase)
0.0to100.0
Crest Factor (per phase)
0.0to100.0
Displacement P.F. (per phase, 3-phase)
0.010 to 1.000 to +0.010
Fundamental Voltages (per phase)
Magnitude 0 to 1,200 kV
Angle 0.0 to 359.9°
Fundamental Currents (per phase)
Magnitude 0 to 32,767 A
Angle 0.0 to 359.9°
Fundamental Real Power (per phase, 3-phase)
0to32,767kW
Fundamental Reactive Power (per phase)
0 to 32,767 kVAR
Harmonic Power (per phase, 3-phase)
0 to 32,767 kW
Phase Rotation ABC or CBA
Unbalance (current and voltage)
0.0to100.0%
Individual Harmonic Magnitudes
0to327.67%
Individual Harmonic Angles
0.0° to 359.9°
Distortion Power 32,767 to 32,767
Distortion Power Factor 0 to 1,000
Readings are obtained only through communications.
K-Factor not available at 400Hz.
Harmonic magnitudes and angles through the 63rd harmonic at 50Hz and 60Hz;
harmonic magnitudes and angles through the 7th harmonic at 400Hz.