The circuit monitor measures currents and voltages and reports in real time
the rms values for all three phases, neutral, and ground current. In addition,
the circuit monitor calculates power factor, real power, reactive power,
and more.
Ta bl e 4 1 lists some of the real-time readings that are updated every second
along with their reportable ranges. When you are viewing real-time readings
from the remote display or
SMS, the circuit monitor is displaying 100-ms
readings.
Table 41: One-Second, Real-Time Readings Samples
Real-Time Readings Reportable Range
Current
Per-Phase 0 to 32,767 A
Neutral
0to32,767A
Ground
0to32,767A
3-PhaseAverage 0to32,767A
Apparent rms 0 to 32,767 A
% Unbalance 0 to ±100.0%
Voltage
Line-to-Line, Per-Phase 0 to 1,200 kV
Line-to-Line, 3-Phase Average 0 to 1,200 kV
Line-to-Neutral, Per-Phase
0to1,200kV
Neutral to Ground
0to1,200kV
Line-to-Neutral, 3-Phase Average 0 to 1,200 kV
% Unbalance
0to100.0%
Real Power
Per-Phase
0 to ± 3,276.70 MW
3-Phase Total 0 to ± 3,276.70 MW
Reactive Power
Per-Phase
0 to ± 3,276.70 MVAR
3-Phase Total 0 to ± 3,276.70 MVAR
Apparent Power
Per-Phase
0 to ± 3,276.70 MVA
3-Phase Total 0 to ± 3,276.70 MVA
PowerFactor(True)
Per-Phase
0.010 to 1.000 to +0.010
3-Phase Total 0.010 to 1.000 to +0.010
PowerFactor(Displacement)
Per-Phase
0.010 to 1.000 to +0.010
3-Phase Total 0.010 to 1.000 to +0.010
Frequency
4565 Hz 23.00 to 67.00 Hz
350450Hz 350.00to450.00Hz
Temperature (Internal Ambient) 100.00°C to +100.00°C
Wye systems only.
REAL-TIME READINGS