Chapter 10Maintenance and Troubleshooting 63230-300-212
Troubleshooting April 2001
© 2001 Schneider Electric All Rights Reserved
126
Cannot communicate with circuit
monitor from a remote personal
computer.
Circuit monitor address is incorrect. Check to see that the circuit monitor is correctly
addressed. See RS-485, RS-232, and Infrared Port
Communications Setupon page 15 for instructions.
Circuit monitor baud rate is incorrect. Verify that the baud rate of the circuit monitor matches the
baud rate of all other devices on its communications link.
See RS-485, RS-232, and Infrared Port Communications
Setupon page 15 for instructions.
Communications lines are improperly
connected.
Verify the circuit monitor communications connections.
Refer to
Chapter 6Communications Connections of the
installation manual for instructions.
Communications lines are improperly
terminated.
Check to see that a multipoint communications terminator
is properly installed. See Terminating the
Communications Linkon page 67 of the installation
manual for instructions.
Incorrect route statement to circuit monitor. Check the route statement. Refer to the SMS online help
for instructions on defining route statements.
Table 101: Troubleshooting