63230-300-212 Appendix BUsing the Command Interface
April 2001 Overview of the Command Interface
185
© 2001 Schneider Electric All Rights Reserved
6209 8019 I/O Data Pointer Preset Accumulated Energies
Requires the IO Data Pointer to point to registers where energy
preset values are entered. All Accumulated energy values must be
entered in the order in which they occur in registers 1700 to 1727.
6210 None None Clears all energies.
6211 None None Clears all accumulated energy values.
6212 None None Clears conditional energy values.
6213 None None Clears incremental energy values.
6214 None None Clears input metering accumulation.
6220 None None Clears all conditional energy values.
6320 None None Disables conditional energy accumulation.
6321 None None Enables conditional energy accumulation.
6910 None None Starts a new incremental energy interval.
Files
7510 8001 Files 116 to trigger Triggers data log entry. Bitmap where Bit 0 = Data Log 1, Bit1 = Data
Log2,Bit2=DataLog3,etc.
7511 8001 File Number Triggers single data log entry.
Setup
9020 None None Enter into setup mode.
9021 8001 1 = Save
2 = Do not save
Exit setup mode and save all changes.
Table B2: Command Codes
Command
Code
Command Parameter
Register
Parameters Description
You must write to register 8001 the number that identifies which output you would like to use. To determine the identifying number, refer to
I/O Point Numberson page 186 for instructions.
Data buffer location (register 8019) is the pointer to the first register where data will be stored. By default, return data begins at register 8020,
although you can use any of the registers from 80208149.
Take care when assigning pointers. Values may be corrupted if two commands
are using the same register.