63230-300-212 Appendix AAbbreviated Register Listing
April 2001 Register Listing
135
© 2001 Schneider Electric All Rights Reserved
1277 Harmonic Current, Neutral B Amps/Scale 0 to 32,767
1278 Harmonic Voltage, A-N/A-B D Volts/Scale 0 to 32,767
1279 Harmonic Voltage, B-N/B-C D Volts/Scale 0 to 32,767
1280 Harmonic Voltage, C-N/C-A D Volts/Scale 0 to 32,767
1281 Total Demand Distortion 0.1% 0 to 1,000
1284 Current, Positive Sequence, Magnitude A Amps/Scale 0 to 32,767
1285 Current, Positive Sequence, Angle 0.1° 0to3,599
1286 Current, Negative Sequence, Magnitude A Amps/Scale 0 to 32,767
1287 Current, Negative Sequence, Angle 0.1° 0to3,599
1288 Current, Zero Sequence, Magnitude A Amps/Scale 0 to 32,767
1289 Current, Zero Sequence, Angle 0.1° 0to3,599
1290 Voltage, Positive Sequence, Magnitude D Volts/Scale 0 to 32,767
1291 Voltage, Positive Sequence, Angle 0.1° 0to3,599
1292 Voltage, Negative Sequence, Magnitude D Volts/Scale 0 to 32,767
1293 Voltage, Negative Sequence, Angle 0.1° 0to3,599
1294 Voltage, Zero Sequence, Magnitude D Volts/Scale 0 to 32,767
1295 Voltage, Zero Sequence, Angle 0.1° 0to3,599
1296 Current, Sequence, Unbalance 0.10% 0 to 32,767
1297 Voltage, Sequence, Unbalance 0.10% 0 to 32,767
Real to Time Minimum Metered Values
1300 Minimum Current, Phase A A Amps/Scale 0 to 32,767
1301 Minimum Current, Phase B A Amps/Scale 0 to 32,767
1302 Minimum Current, Phase C A Amps/Scale 0 to 32,767
1303 Minimum Current, Neutral B Amps/Scale 0 to 32,767
1304 Minimum Current, Ground C Amps/Scale 0 to 32,767
1305 Minimum Current, 3-Phase Average A Amps/Scale 0 to 32,767
1306 Minimum Current, Apparent RMS A Amps/Scale 0 to 32,767
1307 Minimum Current Unbalance, Phase A 0.10% -1,000 to 1,000
1308 Minimum Current Unbalance, Phase B 0.10% -1,000 to 1,000
1309 Minimum Current Unbalance, Phase C 0.10% -1,000 to 1,000
1310 Minimum Current Unbalance, Max 0.10% -1,000 to 1,000
1320 Minimum Voltage, A-B D Volts/Scale 0 to 32,767
1321 Minimum Voltage, B-C D Volts/Scale 0 to 32,767
1322 Minimum Voltage, C-A D Volts/Scale 0 to 32,767
1323 Minimum Voltage, L-L Average D Volts/Scale 0 to 32,767
1324 Minimum Voltage, A-N D Volts/Scale 0 to 32,767
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registers on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.