63230-300-212 Appendix A—Abbreviated Register Listing
April 2001 Register Listing
159
© 2001 Schneider Electric All Rights Reserved
Metering Configuration
3200
Metering System Type
System Connection
30 = 3PH3W2CT
31 = 3PH3W3CT
40 = 3PH4W3CT (default)
41 = 3PH4W4CT
42 = 3PH4W3CT2PT
43 = 3PH4W4CT2PT
——30,31, 40,41,42,43
3201
CT Ratio, Phase Primary — Amps 1 to 32,767, Default = 5
3202
CT Ratio, Phase Secondary — Amps 1, 5, Default = 5
3203
CT Ratio, Neutral Primary — Amps 1 to 32,767, Default = 5
3204
CT Ratio, Neutral Secondary — Amps 1, 5, Default = 5
3205
PT Ratio, Phase Primary — Volts/Scale 1 to 32,767, Default = 120
3206
PT Ratio, Phase Primary Scale Factor
-1 = Direct Connect
——-1 to 2, Default = 0
3207
PT Ratio, Phase Secondary — Volts
100, 110, 115, 120;
Default = 120
3208
Nominal System Frequency — Hertz 50,60,400; Default = 60
3209
Scale A to Phase Amps ——-2 to 1, Default = 0
3210
Scale B to Neutral Amps ——-2 to 1, Default = 0
3211
Scale C to Ground Amps ——-2 to 1, Default = 0
3212
Scale D to Phase Volts ——-1 to 2, Default = 0
3213
Scale E to Neutral Volts ——-1 to 2, Default = -1
3214
Scale F to Power ——-3 to 3, Default = 0
3216
Scale H to Transient Voltages ——0to3,Default=1
Table A–3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See “How Power Factor is Stored in the Register” on page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.