63230-300-212 Chapter 3—Operation
April 2001 Configuring the Circuit Monitor Using The Setup Menu
21
© 2001 Schneider Electric All Rights Reserved
To set up a newly created custom alarm for use by the circuit monitor, use the
Edit Parameters option on the Alarm screen. You can also change
parameters of any alarm, new or existing. For example, using the Edit option
you can enable or disable an alarm, change its priority, and change its pickup
and dropout setpoints.
Follow these instructions to set up or edit an alarm:
1. From the Main Menu, select Setup > Alarm > Edit Parameters.
The Edit Parameters screen displays.
2. Select the Alarm Group:
Standard
High Speed
Disturbance
Digital
Boolean
The Select Alarm screen displays.
NOTE: If you are setting up or editing a digital alarm, alarm names such
as Breaker 1 trip, Breaker 1 reset will display instead.
3. Select the alarm you want to set up or edit.
The Edit Alarm screen with the alarm parameters displays. Table 35
describes the options on this menu.
Setting Up and Editing Alarms
EDIT PARAMETERS
Standard 1 sec
High Speed 100ms
Disturbance <1cycle
Digital
Boolean
SELECT ALARM
*01 Over Ia
02 Over Ib
03 Over Ic
EDIT ALARM
Lbl:Over Ia
Enable No
Priority None
Setpoint Mode Abs
Pickup 0
PU Dly seconds 0
Dropout 0
DO Dly seconds 0