Appendix AAbbreviated Register Listing 63230-300-212
Register Listing April 2001
© 2001 Schneider Electric All Rights Reserved
164
3361
Discrete Input Point Assignment to Discrete Input Status
Bitmap Bit 11
IO Point Number for Discrete Input to include in Discrete Input
Status Bitmap: Bit 11.
0=none,default=38(DigInC4)
——0to66
3362
Discrete Input Point Assignment to Discrete Input Status
Bitmap Bit 12
IO Point Number for Discrete Input to include in Discrete Input
Status Bitmap: Bit 12.
0=none,default=39(DigInC5)
——0to66
3363
Discrete Input Point Assignment to Discrete Input Status
Bitmap Bit 13
IO Point Number for Discrete Input to include in Discrete Input
Status Bitmap: Bit 13.
0=none,default=40(DigInC6)
——0to66
3364
Discrete Input Point Assignment to Discrete Input Status
Bitmap Bit 14
IO Point Number for Discrete Input to include in Discrete Input
Status Bitmap: Bit 14.
0=none,default=41(DigInC7)
——0to66
3365
Discrete Input Point Assignment to Discrete Input Status
Bitmap Bit 15
IO Point Number for Discrete Input to include in Discrete Input
Status Bitmap: Bit 15.
0=none,default=42(DigInC8)
——0to66
Communication
3400
RS-485 Comm Port #1 Operation Mode
0 = Modbus Slave (default)
1 = Jbus Slave
——0to1
3401
RS-485 Comm Port #1 Address
Valid Addresses: (Default = 1)
Modbus:0to247
Jbus: 0 to 255
——0to255
3402
RS-485 Comm Port #1 Baud Rate
0 = 1200
1 = 2400
2 = 4800
3 = 9600 (default)
4 = 19200
5 = 38400
——0to5
3403
RS-485 Comm Port #1 Parity
0 = Even (default)
1=Odd
2=None
——0to2
3430
RS-485 Comm Port #2 Operation Mode
0 = Modbus Slave (default)
1 = Jbus Slave
——0to1
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to0; -0.999 maps to 0.999;0.999 leadingmaps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registerson page 187 for instructions on
howtousethesetup-modecommands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.