Schneider Electric 4000 Car Video System User Manual


 
63230-300-212 Appendix AAbbreviated Register Listing
April 2001 Register Listing
137
© 2001 Schneider Electric All Rights Reserved
1372 Minimum Alternate Displacement Power Factor, Phase A 0.001 0 to 2,000
1373 Minimum Alternate Displacement Power Factor, Phase B 0.001 0 to 2,000
1374 Minimum Alternate Displacement Power Factor, Phase C 0.001 0 to 2,000
1375 Minimum Alternate Displacement Power Factor, Total 0.001 0 to 2,000
1380 Minimum Frequency
0.01 Hertz
0.1 Hertz
(50/60) 2,300 to 6,700
(400) 3,500 to 4,500
1381 Minimum Temperature 0.1 °C -1,000 to 1,000
1390 Minimum Auxiliary Analog Input Value, User-Selected Input 1
Refer to Analog Input
Setup
-32,767 to 32,767
1391 Minimum Auxiliary Analog Input Value, User-Selected Input 2
Refer to Analog Input
Setup
-32,767 to 32,767
1392 Minimum Auxiliary Analog Input Value, User-Selected Input 3
Refer to Analog Input
Setup
-32,767 to 32,767
1393 Minimum Auxiliary Analog Input Value, User-Selected Input 4
Refer to Analog Input
Setup
-32,767 to 32,767
1394 Minimum Auxiliary Analog Input Value, User-Selected Input 5
Refer to Analog Input
Setup
-32,767 to 32,767
1395 Minimum Auxiliary Analog Input Value, User-Selected Input 6
Refer to Analog Input
Setup
-32,767 to 32,767
1396 Minimum Auxiliary Analog Input Value, User-Selected Input 7
Refer to Analog Input
Setup
-32,767 to 32,767
1397 Minimum Auxiliary Analog Input Value, User-Selected Input 8
Refer to Analog Input
Setup
-32,767 to 32,767
1398 Minimum Auxiliary Analog Input Value, User-Selected Input 9
Refer to Analog Input
Setup
-32,767 to 32,767
1399 Minimum Auxiliary Analog Input Value, User-Selected Input 10
Refer to Analog Input
Setup
-32,767 to 32,767
1400 Minimum THD/thd Current, Phase A 0.10% 0 to 32,767
1401 Minimum THD/thd Current, Phase B 0.10% 0 to 32,767
1402 Minimum THD/thd Current, Phase C 0.10% 0 to 32,767
1403 Minimum THD/thd Current, Phase N 0.10% 0 to 32,767
1404 Minimum THD/thd Current, Ground 0.10% 0 to 32,767
1407 Minimum THD/thd Voltage, A-N 0.10% 0 to 32,767
1408 Minimum THD/thd Voltage, B-N 0.10% 0 to 32,767
1409 Minimum THD/thd Voltage, C-N 0.10% 0 to 32,767
1410 Minimum THD/thd Voltage, N-G 0.10% 0 to 32,767
1411 Minimum THD/thd Voltage, A-B 0.10% 0 to 32,767
1412 Minimum THD/thd Voltage, B-C 0.10% 0 to 32,767
1413 Minimum THD/thd Voltage, C-A 0.10% 0 to 32,767
1418 Minimum Current K-Factor, Phase A 0.10 0to10,000
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registers on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.