63230-300-212 Appendix AAbbreviated Register Listing
April 2001 Register Listing
165
© 2001 Schneider Electric All Rights Reserved
3431
RS-485 Comm Port #2 Address
Modbus: 0 to 247
Jbus : 0 to 255
——0to255,Default=1
3432
RS-485 Comm Port #2 Baud Rate
0 = 1200
1 = 2400
2 = 4800
3 = 9600 (default)
4 = 19200
5 = 38400
——0to5
3433
RS-485 Comm Port #2 Parity
0 = Even (default)
1=Odd
2=None
——0to2
3460
Infrared Comm Port, Operation Mode
0 = Modbus Slave (default)
1=JbusSlave
——0to1
3461
Infrared Comm Port, Address
Modbus: 0 to 247
Jbus : 0 to 255
——0to255,Default=1
3462
Infrared Comm Port, Baud Rate
3 = 9600
4 = 19200
5 = 38400 (default)
——3to5
3463
Infrared Comm Port, Parity
0 = Even (default)
1=Odd
2=None
——0to2
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registers on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.